Custom Timers and Intervals
8.1.2 Correlating the timer with an input
To correlate the timer with an input
1. Select the timer that you just created.
2. Click Edit in the Advanced Logic window at the bottom of the Configurator window.
The Advanced Logic Editor appears.
3. Double-click an input from the Inputs list on the left.
The input appears in the Equation window.
4. Type a description for the timer in the Description field.
5. Click OK.
The timer will start when the input activates.
8.1.3 Correlating a zone with the timer
To correlate a zone with the timer
1. Select Input Zones (under Base I/O) in the job tree on the left side of the Configurator
window.
2. Click the Insert menu, and then click Add Zone.
The Add Zone window appears.
3. Click Add to add the zone, and then click Close.
4. Double-click in the Tag column, and then type a name for the zone. Press the Enter key.
5. Select the zone that you just created.
6. Click the Advanced Logic tab at the bottom, and then click Edit.
The Advanced Logic Editor appears.
7. Double-click the timer you created from the Inputs list on the left.
You can identify the timer by the Tag that you gave it. The ID for the timer is something
like **-**-**-TM-016, where TM means “timer” and 016 is the number of the timer. The
Configurator gives each timer a number starting from 16.
The timer you created appears in the Equation box.
8. Click the EQU button.
The EQU operator appears in the Equation box.
9. Click the pulldown menu, click TIMER_EXPIRED, and then click the Sys_Def button.
This equation should look something like this:
**-**-**-TM-016 EQU TIMER_EXPIRED
When timer 16 expires, the equation becomes true and the zone activates.
If you want the zone to activate while the timer is running:
Click TIMER_RUNNING instead of TIMER_EXPIRED. The zone will remain active
while the timer is running. When the timer expires, the zone will become inactive.
10. Type a description in the Description box, and then type a comment in the Comments
box.
11. Click OK to close the Advanced Logic Editor.