Cables
The numbers represent the diameter of the core/cladding in micrometers (microns).
12.3 Typical Optical Power Budget
50/125 μm: 9.6 dB
62.5/125 μm: 15 dB
12.3.1 Connecting Fiber Optic Cables
The FOM-2000-SP Fiber Optics Network Module has 4 connections: RX2, RX1, TX2, and
TX1. R stands for Receive and T stands for Transmit.
Wire the Fiber Optics Network Module from the TX connection to the RX connection,
and from 1 to 2:
Connect a cable from TX1 of node 1 to RX2 of node 2, and a cable from RX1 of node
1 to TX2 of node 2.
Connect a cable from TX1 of node 2 to RX2 of node 3, and a cable from RX1 of node
2 to TX2 of node 3.
See Figure 62.