Existing field geometries
D
elete existing geometries: The field is redrawn according to the surrounding
contour.
Modify existing geometries: The existing field is adapted to the surrounding con‐
tour.
Measuring method
Use any distance value: Each scan of the surrounding contour is used individually
to draw the field.
Use median of the distance values: The median of the last 25 scans is used to
draw the field.
Type of teach-in
Only allow zooming out: The shortest measured distance is used at each angle. If
you walk the imaginary field on its borders and, e.g. hold a board or cardboard into
the laser beam, the surrounding contour is thereby limited.
Allow zooming in: The surrounding contour is used as it is measured.
Automated reduction
You can specify that the proposed field is drawn smaller than the measured surround‐
ing contour so that the field will be at a distance from walls. The default value corre‐
sponds to the value TZ (tolerance zone of the safety laser scanner).
CONFIGURATION 8
8025870/2020-09-04 | SICK O P E R A T I N G I N S T R U C T I O N S | microScan3 Core I/O
101
Subject to change without notice

Table of Contents

Other manuals for SICK microScan3 Core I/O

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SICK microScan3 Core I/O and is the answer not in the manual?

SICK microScan3 Core I/O Specifications

General IconGeneral
BrandSICK
ModelmicroScan3 Core I/O
CategoryScanner
LanguageEnglish

Related product manuals