Reset
T
he reset brings the protective device back to the monitoring state after it has sent
a stop command. The reset also quits the start-up or restart interlock of a protective
device, so that the machine can be restarted in a second step.
The reset must only be possible, when all safety functions and protective devices are
functional.
The reset of the protective device must not introduce any movement or dangerous
situations itself. The machine is only permitted to start after the reset once a separate
start command has been sent.
Manual resets are performed using a separate, manually operated device, such as
a reset pushbutton.
Automatic resets by the protective device are only permitted in special cases, if
one of the following conditions is met:
°
It must not be possible for people to be in the hazardous area without
triggering the protective device.
°
It must be ensured that no people are in the hazardous area during or after
the reset.
Internal restart interlock
Eac
h safety output of the safety laser scanner is equipped with a configurable internal
restart interlock.
With safety outputs via the network, resetting is done via a network signal.
When the internal restart interlock is used, the following sequence is the result for the
machine operator:
1 A safety output of the safety laser scanner switches to the OFF state if there is an
interruption in the protective field.
2 The safety output remains in the OFF state when there is no longer an object in
the protective field.
3 The safety output only switches back to the ON state when the operator presses
the reset pushbutton, which is outside the hazardous area. If there is an object in
the protective field when the reset pushbutton is pressed, the safety output stays
in the OFF state.
4 After the reset, the operator can restart the machine in a second step.
PROJECT PLANNING 4
8021219/1ELL/2022-01-21 | SICK O P E R A T I N G I N S T R U C T I O N S | microScan3 – PROFINET
63
Subject to change without notice

Table of Contents

Other manuals for SICK microScan3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SICK microScan3 and is the answer not in the manual?

SICK microScan3 Specifications

General IconGeneral
Scanning angle275°
Power supply24 V DC
Supply voltage24 V DC ± 20%
Enclosure ratingIP65
Resolution70 mm
Protective field range5.5 m
Number of fields128
InterfaceEthernet
Safety integrity levelSIL3
Performance levelPL e
Ambient temperature+50°C
Scanning range5.5 m