Alarms, faults and system messages
9.4 Faults
Converter with the CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2016, FW V4.7 SP6, A5E34259001B AC
409
Image 9-7 Complete fault buffer
Acknowledgement
You have multiple options to acknowledge a fault, e.g.:
PROFIdrive control word 1, bit 7 (r2090.7)
Acknowledge via the Operator Panel
Switch-off the inverter power supply and switch-on again.
Faults detected during the inverter-internal monitoring of hardware and firmware can be
acknowledged only by switching the supply voltage off and on again. The list of faults in the
List Manual contains a note on this limited acknowledgement possibility.
Emptying the fault buffer: Fault history
The fault history can contain up to 56 faults.
The acknowledgement has no effect as long as none of the causes for the faults in the buffer
have been removed. If at least one of the faults in the fault buffer has been removed (the
cause of the fault has been removed) and you acknowledge the faults, then the following
happens:
1. The inverter accepts all faults from the fault buffer in the first eight memory locations of
the fault history (indexes 8 ... 15).
2. The inverter deletes the faults that have been removed from the fault buffer.
3. The inverter writes the time of acknowledgement of the faults that have been removed
into parameters r2136 and r2109 (fault time removed).