Alarms, faults and system messages
9.4 Faults
Converter with the CU240B-2 and CU240E-2 Control Units
410 Operating Instructions, 01/2016, FW V4.7 SP6, A5E34259001B AC
Image 9-8 Fault history after acknowledging the faults
After acknowledgement, the faults that have not been removed are located in the fault buffer
as well as in the fault history. For these faults, the "fault time coming" remains unchanged
and the "fault time removed" remains empty.
If less than eight faults were shifted or copied into the fault history, the memory locations with
the higher indexes remain empty.
The inverter shifts the values previously saved in the fault history by eight indexes. Faults,
which were saved in indexes 5663 before the acknowledgement, are deleted.
Deleting the fault history
If you wish to delete all faults from the fault history, set parameter p0952 to zero.