Alarms, faults and system messages
9.4 Faults
Converter with the CU240B-2 and CU240E-2 Control Units
412 Operating Instructions, 01/2016, FW V4.7 SP6, A5E34259001B AC
Extended settings for faults
You can modify the motor fault response for up to 20 different fault codes:
p2100
Setting the fault number for fault response
Selecting the faults for which the fault response should be changed
p2101
Setting the fault response for the selected fault
You can modify the acknowledgement type for up to 20 different fault codes:
p2126
Setting the fault number for the acknowledgement mode
Selection of the faults for which the acknowledgement type should be changed
p2127
Setting, acknowledgement mode
Setting the acknowledgement type for the selected fault
1: Can only be acknowledged using POWER ON
2: IMMEDIATE acknowledgement after removing the fault cause
You can change up to 20 different faults into an alarm, or suppress faults:
p2118
Setting the message number for the message type
Selection of the message for which the message type should be changed
p2119
Setting the message type for the selected fault
1: Fault
2: Alarm
You will find details in function diagram 8075 and in the parameter description of the List
Manual.