Alarms, faults and system messages
9.5 List of alarms and faults
Converter with the CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2016, FW V4.7 SP6, A5E34259001B AC
419
Number
Cause
Remedy
F13101 Know-how protection: Copy protec-
tion cannot be activated
Insert a valid memory card.
F30001 Overcurrent Check the following:
Motor data, if required, carry out commissioning
Motor connection method (Υ / Δ)
V/f operation: Assignment of rated currents of motor and Power Mod-
ule
Line quality
Make sure that the line commutating reactor is connected properly
Power cable connections
Power cables for short-circuit or ground fault
Power cable length
Line phases
If this doesn't help:
V/f operation: Increase the acceleration ramp
Reduce the load
Replace the power unit
F30002 DC-link voltage overvoltage Increase the ramp-down time (p1121).
Set the rounding times (p1130, p1136).
Activate the DC-link voltage controller (p1240, p1280).
Check the line voltage (p0210).
Check the line phases.
F30003
DC-link voltage undervoltage
Check the line voltage (p0210).
F30004 Inverter overtemperature Check whether the inverter fan is running.
Check whether the ambient temperature is in the permissible range.
Check whether the motor is overloaded.
Reduce the pulse frequency.
F30005 I2t inverter overload Check the rated currents of the motor and Power Module.
Reduce the current limit p0640.
When operating with V/f characteristic: Reduce p1341.
F30011 Line phase failure Check the inverter's input fuses.
Check the motor feeder cables.
F30015 Motor cable phase failure Check the motor cables.
Increase the ramp-up or ramp-down time (p1120).
F30021 Ground fault
Check the power cable connections.
Check the motor.
Check the current transformer.
Check the cables and contacts of the brake connection (a wire might
be broken).
F30027 Time monitoring for DC-link pre-
charging
Check the line voltage at the input terminals.
Check the line voltage setting (p0210).
F30035 Overtemperature, intake air
Check whether the fan is running.