Alarms, faults and system messages
9.5 List of alarms and faults
Converter with the CU240B-2 and CU240E-2 Control Units
420 Operating Instructions, 01/2016, FW V4.7 SP6, A5E34259001B AC
Number
Cause
Remedy
F30036 Overtemperature, inside area
Check the fan filter elements.
Check whether the ambient temperature is in the permissible range.
F30037 Rectifier overtemperature See F30035 and, in addition:
Check the motor load.
Check the line phases
A30049
Internal fan defective
Check the internal fan and if required replace.
F30059 Internal fan defective Check the internal fan and if required replace.
A30502 DC-link overvoltage
Check the unit supply voltage (p0210).
Check the dimensioning of the line reactor.
A30920 Temperature sensor fault Check that the sensor is connected correctly.
A50001 PROFINET configuration error A PROFINET control is attempting to establish a connection with an in-
correct configuration telegram. Check whether "Shared Device" is activat-
ed (p8929 = 2).
A50010
PROFINET name of station invalid
Correct the name of station (p8920) and activate (p8925 = 2).
A50020 PROFINET: Second control miss-
ing
"Shared Device" is activated (p8929 = 2). However, only the connection
to a PROFINET control is available.
For further information, please refer to the List Manual.
For further information, please refer to the List Manual.