Technical data
10.3 Technical data, Power Modules
Converter with the CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2016, FW V4.7 SP6, A5E34259001B AC
433
Table 10- 3 PM240-2, IP20, frame sizes B, 1 AC / 3 AC 200 V … 240 V
Article No. - without filter
Article No. - with filter
LO base load power
LO base load input current 1 AC
LO base load input current 3 AC
LO base load output current
1.1 kW
13.5 A
7.8 A
1.5 kW
18.1 A
9.7 A
2.2 kW
24.0 A
13.6 A
HO base load power
HO base load input current 1 AC
HO base load input current 3 AC
HO base load output current
0.75 kW
11.8 A
5.5 A
1.1 kW
15.8 A
7.8 A
1.5 kW
20.9 A
9.7 A
Fuse according to IEC
3NE 1814-0 (20 A)
3NE 1815-0 (25 A)
3NE 1803-0 (35 A)
Power losses without filter
0.05 kW
0.07 kW
0.12 kW
Required cooling air flow
Weight without filter
2.8 kg
2.8 kg
2.8 kg
Table 10- 4 PM240-2, PT, frame sizes B, 1 AC / 3 AC 200 V … 240 V
Article No. - without filter
Article No. - with filter
LO base load power
LO base load input current 1 AC
LO base load input current 3 AC
LO base load output current
2.2 kW
24.0 A
13.6 A
HO base load power
HO base load input current 1 AC
HO base load input current 3 AC
HO base load output current
1.5 kW
20.9 A
9.7 A
7.4 A
Fuse according to IEC
3NE 1803-0 (35 A)
Power losses without filter
0.12 kW
1)
1)
Required cooling air flow
Weight without filter
3.4 kg
1) approx. 0.08 through the heatsink