Technical data
10.3 Technical data, Power Modules
Converter with the CU240B-2 and CU240E-2 Control Units
434 Operating Instructions, 01/2016, FW V4.7 SP6, A5E34259001B AC
Table 10- 5 PM240-2, IP 20, frame sizes C, 1 AC / 3 AC 200 V … 240 V
Article No. - without filter
Article No. - with filter
...1PB21-4UL0
…1PB21-4AL0
…1PB21-8UL0
...1PB21-8AL0
LO base load power
LO base load input current 1 AC
LO base load input current 3 AC
LO base load output current
3 kW
35.9 A
17.7 A
4 kW
43.0 A
22.8 A
HO base load power
HO base load input current 1 AC
HO base load input current 3 AC
HO base load output current
2.2 kW
31.3 A
13.6 A
3 kW
37.5 A
17.7 A
Fuse according to IEC
3NE 1817-0 (50 A)
3NE 1818-0 (63 A)
Power losses without filter
0.14 kW
0.18 kW
Required cooling air flow
Weight without filter
5.0 kg
5.0 kg
Table 10- 6 PM240-2, PT, frame sizes C, 1 AC / 3 AC 200 V … 240 V
Article No. - without filter
Article No. - with filter
...1PB21-8UL0
…1PB21-8AL0
LO base load power
LO base load input current 1 AC
LO base load input current 3 AC
LO base load output current
4 kW
43.0 A
22.8 A
HO base load power
HO base load input current 1 AC
HO base load input current 3 AC
HO base load output current
3 kW
37.5 A
17.7 A
13.6 A
Fuse according to IEC
Fuse according to UL
3NE 1818-0 (63 A)
50 A Class J
Power losses without filter
0.18 kW
1)
1)
Required cooling air flow
Weight without filter
5.9 kg
1) approx. 0.09 through the heatsink