Technical data
10.3 Technical data, Power Modules
Converter with the CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2016, FW V4.7 SP6, A5E34259001B AC
437
Article number
LO base load output current for a pulse frequency of …
[A]
2 kHz /
4 kHz
6 kHz
8 kHz
10 kHz
12 kHz
14 kHz
16 kHz
6SL3210-1PB13-0❒L0
3.2
2.6
2.1
1.8
1.5
1.4
1.2
6SL321❒-1PB13-8❒L0
4.2
3.3
2.7
2.3
2.0
1.8
1.6
6SL3211-1PB15-5❒L0
6.0
4.7 3.9 3.3 2.8 2.5 2.2
6SL3210-1PB17-4❒L0
7.4
6.3
5.2
4.4
3.7
3.3
3.0
6SL321❒-1PB21-0❒L0
10.4
8.8
7.3
6.2
5.2
4.7
4.2
6SL3210-1PB21-4❒L0
13.6
11.6
9.5
8.2
6.8
6.1
5.4
6SL321❒-1PB21-8❒L0
17.5
14.9
12.3
10.5
8.8
7.9
7.0
6SL3210-1PC22-2❒L0
22.0
18.7
15.4
13.2
11.0
9.9
8.8
6SL3210-1PC22-8❒L0
28.0
23.8
19.6
16.8
14.0
12.6
11.2
6SL3210-1PC24-2❒L0
42
35.7
29.4
25.2
21.0
18.9
16.8
6SL3210-1PC25-4❒L0
54
45.9
37.8
32.4
27.0
24.3
21.6
6SL3210-1PC26-8❒L0
68
57.8
47.6
40.8
34.0
30.6
27.2
6SL3210-1PC28-8❒L0
80
68.0
56.0
48.0
40.0
36.0
32.0
6SL3210-1PC31-1❒L0
104
88.4
72.8
62.4
52.0
46.8
41.6
6SL3210-1PC31-3❒L0
130
110.5
91.0
---
---
---
---
6SL3210-1PC31-6❒L0
154
130.9
107.8
---
---
---
---
6SL3210-1PC31-8❒L0
178
151.3
124.6
---
---
---
---
The permissible motor cable length depends on the particular cable type and the pulse frequency that