Table 10- 34 PM240, IP20, frame sizes F, 3-phase 380480 VAC
Article no. - without filter
Article no. - with filter
6SL3224-…
6SL3224-…
…0BE34-5UA0
…0BE34-5AA0
…0BE35-5UA0
…0BE35-5AA0
…0BE37-5UA0
…0BE37-5AA0
LO base load power
LO base load input current
LO base load output current
55 kW
129 A
110 A A
75 kW
168 A
145 A
90 kW
204 A
178 A
HO base load power
HO base load input current
HO base load output current
45 kW
108 A
90 A
55 kW
132 A
110 A
75 kW
169 A
145 A
Fuse according to UL (SIEMENS)
Fuse according to UL (Class J)
3NE1224-0
150 A, 600 V
3NE1225-0
200 A, 600 V
3NE1227-0
250 A, 600 V
Power losses without filter
Power losses with filter
1.4 kW
1.5 kW
1.9 kW
2.0 kW
2.3 kW
2.4 kW
Required cooling air flow
94 l/s
94 l/s
117 l/s
Weight without filter
Weight with filter
36 kg
52 kg
36 kg
52 kg
36 kg
52 kg
Table 10- 35 PM240, IP20, frame sizes F, 3-phase 380480 VAC
Article no. - without filter
6SL3224-…
…0BE38-8UA0
…0BE41-1UA0
LO base load power
LO base load input current
LO base load output current
110 kW
234 A
205 A
132 kW
284 A
250 A
HO base load power
HO base load input current
HO base load output current
90 kW
205 A
178 A
110 kW
235 A
205 A
Fuse according to UL (SIEMENS)
Fuse according to UL (Class J)
3NE1227-0
300 A, 600 V
3NE1230-0
400 A, 600 V
Power loss
2.4 kW
2.5 kW
Required cooling air flow 117 l/s 117 l/s
Cross section of line and motor cables 95120 mm
2
3/04/0 AWG
95120 mm
2
3/04/0 AWG
Tightening torque for line and motor cables
13 Nm / 115 lbf in
13 Nm / 115 lbf in
Weight 39 kg 39 kg