Technical data
10.3 Technical data, Power Modules
Converter with the CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2016, FW V4.7 SP6, A5E34259001B AC
457
Table 10- 34 PM240, IP20, frame sizes F, 3-phase 380 … 480 VAC
Article no. - without filter
Article no. - with filter
LO base load power
LO base load input current
LO base load output current
55 kW
129 A
75 kW
168 A
90 kW
204 A
HO base load power
HO base load input current
HO base load output current
45 kW
108 A
55 kW
132 A
75 kW
169 A
Fuse according to UL (SIEMENS)
Fuse according to UL (Class J)
3NE1224-0
3NE1225-0
3NE1227-0
Power losses without filter
1.4 kW
1.9 kW
2.3 kW
Required cooling air flow
Weight without filter
36 kg
36 kg
36 kg
Table 10- 35 PM240, IP20, frame sizes F, 3-phase 380 … 480 VAC
Article no. - without filter
LO base load power
LO base load input current
LO base load output current
110 kW
234 A
132 kW
284 A
HO base load power
HO base load input current
HO base load output current
90 kW
205 A
110 kW
235 A
Fuse according to UL (SIEMENS)
Fuse according to UL (Class J)
3NE1227-0
3NE1230-0
Required cooling air flow 117 l/s 117 l/s
Cross section of line and motor cables 95 … 120 mm
2
95 … 120 mm
2
Tightening torque for line and motor cables
Weight 39 kg 39 kg