Loading...
Technical data
10.3 Technical data, Power Modules
Converter with the CU240B-2 and CU240E-2 Control Units
456 Operating Instructions, 01/2016, FW V4.7 SP6, A5E34259001B AC
Table 10- 32 PM240, IP20, frame sizes D, 3-phase 380480 VAC
Article no. - without filter
Article no. - with filter
6SL3224-…
6SL3224-…
…0BE31-5UA0
…0BE31-5AA0
…0BE31-8UA0
…0BE31-8AA0
…0BE32-2UA0
…0BE32-2AA0
LO base load power
LO base load input current
LO base load output current
18.5 kW
46 A
38 A
22 kW
53 A
45 A
30 kW
72 A
60 A
HO base load power
HO base load input current
HO base load output current
15 kW
40 A
32 A
18.5 kW
46 A
38 A
22 kW
56 A
45 A
Fuse according to UL (SIEMENS)
Fuse according to UL (Class J)
3NE1817-0
---
3NE1818-0
---
3NE1820-0
---
Power loss 0.44 kW
0.42 kW
0.55 kW
0.52 kW
0.72 kW
0.69 kW
Required cooling air flow
22 l/s
22 l/s
39 l/s
Weight without filter
Weight with filter
13 kg
16 kg
13 kg
16 kg
13 kg
16 kg
Table 10- 33 PM240, IP20, frame sizes E, 3-phase 380480 VAC
Article no. - without filter
Article no. - with filter
6SL3224-…
6SL3224-…
…0BE33-0UA0
…0BE33-0AA0
…0BE33-7UA0
…0BE33-7AA0
LO base load power
LO base load input current
LO base load output current
37 kW
88 A
75 A
45 kW
105 A
90 A
HO base load power
HO base load input current
HO base load output current
30 kW
73 A
60 A
37 kW
90 A
75 A
Fuse according to UL (SIEMENS)
Fuse according to UL (Class J)
3NE1021-0
---
3NE1022-0
---
Power losses without filter
Power losses with filter
0.99 kW
1.04 kW
1.2 kW
1.2 kW
Required cooling air flow
22 l/s
39 l/s
Weight without filter
Weight with filter
16 kg
23 kg
16 kg
23 kg