Instructions   
11.1 S7-1500 Motion Control V2 
  S7-1500 Motion Control V13 Update 3 
236  Function Manual, 07/2014, A5E03879256-AC 
The job is being executed. 
Error  OUTPUT  BOOL  FALSE  TRUE  An error occurred in Motion Control instruction 
MC_Power. The cause of the error can be found in 
Error ID (Page 386) for parameter "Error" 
Enabling technology objects 
To enable a technology object, set the Enable parameter to TRUE. 
If the Status parameter shows the value TRUE , then the technology object is enabled.  
If an axis is in motion when the technology object is enabled (actual velocity is present), then 
the axis brakes to the setpoint zero, using the maximum deceleration configured in 
"Technology object > Configuration > Extended parameters > Dynamic limits" 
(<TO>.DynamicLimits.MaxDeceleration). This braking ramp can be overridden by Motion 
Control jobs. 
 
Note 
Automatic enabling after acknowledgement of a technology alarm 
If the technology object is disabled due to a technology alarm, then it will automatically be 
enabled again after the cause has been eliminated and the alarm has been acknowledged. 
This requires the Enable parameter to have retained the value TRUE dur
ing this process. 
Disabling technology objects 
To disable a technology object, set the Enable parameter to FALSE. 
If an axis is in motion, then it will be braked to a standstill according to the selected 
"StopMode". 
If the "Busy" and "Status" parameters show the value FALSE , then the disabling of the 
technology object has been completed.