DynamicDefaults tags (positioning axis/synchronous axis)
The tag structure <TO>.DynamicDefaults.<tag name> contains the configuration of the
dynamic defaults. These settings will be used, if you specify a dynamic value less than 0.0 in
a Motion Control instruction (exceptions: MC_MoveJog.Velocity, MC_MoveVelocity.Velocity).
Changes to the dynamic defaults will be applied with the next rising edge at the "Execute"
parameter of a Motion Control instruction.
Legend (Page 332)
Emergency stop deceleration
Evaluating the technology data block (Page 173)
PositionLimits_SW tags (positioning axis/synchronous axis)
The tag structure <TO>.PositionLimits_SW.<tag name> contains the configuration for
position monitoring with software limit switches. Software limit switches are used to limit the
operating range of a positioning axis.
Legend (Page 332)
Active BOOL - DIR FALSE: Monitoring disabled
MinPosition LREAL -1.0E12 to
DIR Position of negative software limit switches
MaxPosition LREAL -1.0E12 to
DIR Position of positive software limit switches
("MaxPosition" > "MinPosition")