Instructions   
11.2 S7-1500 Motion Control V1 
  S7-1500 Motion Control V13 Update 3 
288  Function Manual, 07/2014, A5E03879256-AC 
●  The technology object has been configured correctly. 
●  "HomingMode" = 2, 3, 4, 5, 8  
The technology object must be enabled. 
●  "HomingMode" = 0, 1, 2, 6, 7  
The encoder values must be valid. (<TO>.StatusSensor[n].State = 2) 
●  An MC_Home job for passive homing is aborted by: 
–  Disabling the technology object by means of "MC_Power.Enable" = FALSE 
–  "MC_Home" job with parameter "HomingMode" = 4, 5, 9 
●  An "MC_Home" job for passive homing does not abort any other Motion Control jobs. 
●  An "MC_Home" job for active homing is aborted by: 
–  Disabling the technology object with "MC_Power.Enable" = FALSE 
–  "MC_Home" job "HomingMode" = 4, 5 
–  "MC_Halt" job 
–  "MC_MoveAbsolute" job 
–  "MC_MoveRelative" job 
–  "MC_MoveVelocity" job 
–  "MC_MoveJog" job 
●  An "MC_Home" job for active homing aborts the following running Motion Control jobs. 
–  "MC_Home" job with parameter "HomingMode" = 2, 3, 4, 5 
–  "MC_Halt" job 
–  "MC_MoveAbsolute" job 
–  "MC_MoveRelative" job 
–  "MC_MoveVelocity" job 
–  "MC_MoveJog" job