Electrical installation
4.10 Signal connections
Inverter chassis units
Operating Instructions, 07/2016, A5E00331449A
105
X500, X501: DRIVE-CLiQ interface
Table 4- 34 DRIVE-CLiQ interface X500 and X501
Pin
Signal name
Technical data
1
TXP
Transmit data +
2 TXN Transmit data -
3
RXP
Receive data +
4
Reserved, do not use
5
Reserved, do not use
6
RXN
Receive data -
7
Reserved, do not use
8
Reserved, do not use
A
+ (24 V)
Power supply
B
M (0 V)
Electronics ground
Blanking plate for DRIVE-CLiQ interfaces (50 pcs.) Article number: 6SL3066-4CA00-0AA0
X524: Electronic power supply
Table 4- 35 Terminal block X524
Terminal
Function
Technical data
+ Electronic power
supply
Voltage: 24 V DC (20.4 to 28.8 V)
Current consumption: max. 1.0 A
(without DRIVE-CLiQ or digital outputs)
Max. current via jumper in connector: 20 A (15 A
according to UL/CSA)
+
Not assigned
M
Electronics ground
M Electronics ground
Max. connectable cross-section: 2.5 mm²
The maximum cable length that can be connected is 10 m.
Note
The two "+" and "M" terminals are jumpered in the connector. This ensures that the supply
voltage is looped through.
The current consumption increases by the value for the DRIVE
-CLiQ participant and digital
outputs.
Note
The ter
minal block must be screwed on tightly using a flat-bladed screwdriver.