Functions, monitoring, and protective functions
9.2 Drive functions
Inverter chassis units
438 Operating Instructions, 07/2016, A5E00331449A
Replacing a defective memory card or a defective Control Unit at the end customer
Assumptions:
The drive is protected with know-how protection and memory card copy protection
The end customer has a replacement memory card and/or a replacement Control Unit on-
site
The required STARTER project has not been saved by the end customer.
The machine manufacturer has the same type of Control Unit as the end customer.
Sequence:
The end customer tells the machine manufacturer the serial number of the memory card
and the Control Unit.
The machine manufacturer links the STARTER project with the serial numbers of the
memory card (p7769) and the Control Unit (p7759).
The machine manufacturer loads the STARTER project into the drive unit.
Online, the machine manufacturer activates, after the download, the copy protection and
the know-how protection (p7765, p7767, p7768).
The machine manufacturer saves the project using p0971 or p0977 onto the memory
card.
The machine manufacturer takes the PS-ACX and possibly generated DCC-YDB files
from the "..\USER\SINAMICS\DATA" area of the memory card and sends them to the end
customer. (for example by E-mail).
The end customer copies the files into the "..\USER\SINAMICS\DATA" area of his
memory card, inserts this into the Control Unit and switches on the drive unit.
After power-up, the end customer saves the project (using p0971 or p0977); if required,
parameters must be reentered from the OEM exception list.
9.2.21.8
Overview of important parameters
r7758[0...19]
KHP Control Unit serial
number
p7759[0...19]
KHP Control Unit reference serial number
r7760
Write protection/know
-how protection status
p7761
Write protection
p7762
Write protection multi
-master fieldbus system access behavior
p7763
KHP OEM exception list number of indices f
or p7764
p7764[0...n]
KHP OEM exception list
p7765
KHP memory card copy protection
p7766[0...29]
KHP password input
p7767[0...29]
KHP password new
p7768[0...29]
KHP password confirmation