Functions, monitoring, and protective functions
9.2 Drive functions
Inverter chassis units
410 Operating Instructions, 07/2016, A5E00331449A
Parameters
p0300:
Mot type selection
p0491
Motor encoder fault response: ENCODER
p1226
Threshold for standstill detection
p1230
BI: Armature short
-circuit/DC braking activation
p1231
Armature short
-circuit/DC braking configuration
4: Internal armature short-circuit/DC braking
5: DC braking OFF1/OFF3
14: DC braking below starting speed
p1232
DC braking, braking current
p1233
DC braking duration
p1234
Speed at the start of DC braking
r1239
CO/BO: Armature short
-circuit/DC braking status word
p2100
Changing the fault reaction, fault number
p2101
Changing the fault reaction, reaction
9.2.10
Increasing the output frequency
9.2.10.1
Description
In applications that require higher output frequencies, the pulse frequency of the converter
may have to be increased.
It may also be necessary to change the pulse frequency to prevent resonances from
occurring.
Since increasing the pulse frequency also increases the switching losses, a derating factor
for the output current must be taken into account when the drive is configured.
Once the pulse frequency has been increased, the new output currents are automatically
included in the calculation for power unit protection.
Note
Use of a sine-wave filter
Use of a sine
-wave filter must be selected using p0230 = 3/4 when carrying out
commissioning. This setting fixes the output frequency to 4 kHz or 2.5 kHz (this cannot be
changed).