Setpoint channel and closed-loop control
7.3 V/f control
Inverter chassis units
334 Operating Instructions, 07/2016, A5E00331449A
Parameter
r0056.5
Voltage boost at startup active/inactive
r0056.6
Acceleration voltage active/inactive
p0304
Rated motor voltage
p0305
Rated motor current
r0395
Stator resistance, actual
p1310
Starting current (voltage boost)
permanent
p1311
Starting current (voltage boost) when accelerating
p1312
Starting current (voltage boost) when starting
r1315
Voltage boost total
7.3.2
Resonance damping
Description
Resonance damping damps oscillations in the active current, which often occur during no-
load operation.
The resonance damping is active in a range from approximately 6% of the rated motor
frequency (p0310). The switch-off frequency is determined by p1349.
For p1300 = 5 and 6 (textiles) the resonance damping is internally disabled in order to be
able to precisely set the output frequency.
Figure 7-9 Resonance damping