EasyManua.ls Logo

Siemens SINAMICS G130 - Know-How Protection

Siemens SINAMICS G130
610 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Functions, monitoring, and protective functions
9.2 Drive functions
Inverter chassis units
432 Operating Instructions, 07/2016, A5E00331449A
9.2.21
Know-how protection
9.2.21.1
Description
The know-how protection is used, for example, so that machine manufacturers can encrypt
their configuration know-how and protect it against changes and copying.
For know-how protection, a password is required; saved data is encrypted.
When know-how protection is activated, most of the setting parameters cannot be changed
and cannot be read out. The display parameters are shown unchanged. The contents of
screen forms in STARTER are not displayed.
Know-how protection can be combined with copy protection.
Characteristics when know-how protection is activated
Except for a small number of system parameters and the parameters specified in an
exception list, all other parameters are locked.
The values of these parameters are not visible in the expert list and so cannot be
changed. The text "know-how protected" appears instead of the parameter values.
Know-how protected parameters can be hidden in the expert list. This requires that the
"not know-how protected" filter is set in the "Online value" column.
The values of display parameters remain visible.
The contents of screen forms are not displayed when know-how protection is active.
Know-how protection can be combined with copy protection.
The same know-how protection is used for scripts.
The drive unit as well as the drive objects and DCC charts therein can be displayed as
inconsistent.
Functions, which can be executed when know-how protection is active
The following functions can be executed although know-how protection is active:
Restoring factory settings
Saving parameters
Acknowledging faults
Displaying faults and alarms
Displaying the history of faults and alarms
Reading out the diagnostic buffer
Switching over to the control panel (complete control panel functionality: Fetch master
control, all buttons and setting parameters)
Displaying created acceptance documentation