Technical specifications
12.2 General specifications
Inverter chassis units
Operating Instructions, 07/2016, A5E00331449A
557
Ambient temperature -25 ... +55 °C -25 ... +70 °C
0
... +40 °C
up to 55 °C with derating
Humidity range
2)
(non-condensing)
corresponds to class
5 to 95%
1K4 according to EN 60721-
5 ... 95% at 40° C
2K3 according to EN 60721-
5 ...
95%
3K3 according to EN 60721-
Environmental class/harmful
2)
1C2 to EN 60721-3-1 2C2 to EN 60721-3-2 3C2 to EN 60721-3-3
Organic/biological influences
2)
1B1 to EN 60721-3-1 2B1 to EN 60721-3-2 3B1 to EN 60721-3-3
2 according to EN 61800-5-1
Installation altitude Up to 2000 m above sea level without derating,
> 2000 m above sea level with derating (see "Derating data")
Vibrational load
2)
- Displacement
- Acceleration
1.5 mm at
5
to 9 Hz
5 m/s² at > 9 to 200 Hz
3.1 mm
at
5
... 9 Hz
10 m/s² at > 9 ... 200 Hz
0.075 mm at 10 ... 58 Hz
10 m/s² at >58 ... 200 Hz
Shock load
2)
- Acceleration
40 m/s² at 22 ms
100 m/s² at 11 ms
100 m/s² at 11 ms
Deviations from the defined classes are shown in
italics
.
1)
Applies to cable lengths of up to 100 m.
2)
The EN standards specified are the European editions of the international IEC standards
with the same designations.
Current derating as a function of the ambient temperature
Permissible output current as a function of the ambient temperature
The devices and the associated system components are rated for an ambient temperature of
40° C and installation altitudes up to 2000 m above sea level. The output current must be
reduced if the devices are operated at ambient temperatures above 40° C. Ambient
temperatures above 55 °C are not permissible. The following table specifies the permissible
output current as a function of the ambient temperature.
Table 12- 2 Current derating as a function of the ambient temperature (air inlet temperature)
Installation altitude
above sea level in m
Current derating factor (in % of rated current)
at an ambient temperature (air inlet temperature) of