Technical specifications
12.2 General specifications
Inverter chassis units
Operating Instructions, 07/2016, A5E00331449A
557
Ambient conditions
Storage
Transport
Operation
Ambient temperature -25 ... +55 °C -25 ... +70 °C
from
40 °C
for 24 hours
0
... +40 °C
up to 55 °C with derating
Humidity range
2)
(non-condensing)
corresponds to class
5 to 95%
1K4 according to EN 60721-
3-1
5 ... 95% at 40° C
2K3 according to EN 60721-
3-2
5 ...
95%
3K3 according to EN 60721-
3-3
Environmental class/harmful
chemical substances
2)
1C2 to EN 60721-3-1 2C2 to EN 60721-3-2 3C2 to EN 60721-3-3
Organic/biological influences
2)
1B1 to EN 60721-3-1 2B1 to EN 60721-3-2 3B1 to EN 60721-3-3
Degree of pollution
2 according to EN 61800-5-1
Installation altitude Up to 2000 m above sea level without derating,
> 2000 m above sea level with derating (see "Derating data")
Mechanical strength
Storage
Transport
Operation
Vibrational load
2)
- Displacement
- Acceleration
corresponds to class
1.5 mm at
5
to 9 Hz
5 m/s² at > 9 to 200 Hz
1M2 to EN 60721-3-1
3.1 mm
at
5
... 9 Hz
10 m/s² at > 9 ... 200 Hz
2M2 to EN 60721-3-2
0.075 mm at 10 ... 58 Hz
10 m/s² at >58 ... 200 Hz
-
Shock load
2)
- Acceleration
corresponds to class
40 m/s² at 22 ms
1M2 to EN 60721-3-1
100 m/s² at 11 ms
2M2 to EN 60721-3-2
100 m/s² at 11 ms
3M4 to EN 60721-3-3
Deviations from the defined classes are shown in
italics
.
1)
Applies to cable lengths of up to 100 m.
2)
The EN standards specified are the European editions of the international IEC standards
with the same designations.
12.2.1
Derating data
12.2.1.1
Current derating as a function of the ambient temperature
Permissible output current as a function of the ambient temperature
The devices and the associated system components are rated for an ambient temperature of
40° C and installation altitudes up to 2000 m above sea level. The output current must be
reduced if the devices are operated at ambient temperatures above 40° C. Ambient
temperatures above 55 °C are not permissible. The following table specifies the permissible
output current as a function of the ambient temperature.
Table 12- 2 Current derating as a function of the ambient temperature (air inlet temperature)
Installation altitude
above sea level in m
Current derating factor (in % of rated current)
at an ambient temperature (air inlet temperature) of
20° C
25° C
30° C
35° C
40° C
45° C
50° C
55° C
0 ... 2000
100%
100%
100%
100%
100%
93.3%
86.7%
80.0%