EasyManua.ls Logo

Siemens SINAMICS G130 - 11 Maintenance

Siemens SINAMICS G130
610 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Maintenance and servicing
11.3 Maintenance
Inverter chassis units
Operating Instructions, 07/2016, A5E00331449A
511
11.3
Maintenance
11.3.1
Maintenance
Servicing involves activities and procedures for maintaining and restoring the specified
condition of the device.
Required tools
The following tools are required for replacing components:
Standard set of tools with screwdrivers, screw wrenches, socket wrenches, etc.
Torque wrenches 1.5 Nm up to 100 Nm
600 mm extension for socket wrenches
Tightening torques for screw connections
The following tightening torques apply when tightening current-conducting connections (DC
link connections, motor connections, busbars, lugs) and other connections (ground
connections, protective conductor connections, steel threaded connections).
Table 11- 1 Tightening torques for screw connections
Thread
Ground connections, protective
conductor connections, steel
threaded connections
Aluminum threaded connections,
plastic, busbars, lugs
M3
1.3 Nm
0.8 Nm
M4 3 Nm 1.8 Nm
M5
6 Nm
3 Nm
M6
10 Nm
6 Nm
M8
25 Nm
13 Nm
M10
50 Nm
25 Nm
M12
88 Nm
50 Nm
M16
215 Nm
115 Nm
Note
Screw connections for protective covers
The threaded connections for the protective covers made of Makrolon may only tightened
with 2.5 Nm.

Table of Contents

Other manuals for Siemens SINAMICS G130

Related product manuals