Functions, monitoring, and protective functions
9.2 Drive functions
Inverter chassis units
Operating Instructions, 07/2016, A5E00331449A
433
Note
List of the exceptions when know-how protection is activated
A list of the adjustable parameters which, in spite of activated know
-how protection, can be
changed, is provided in the List Manual.
The list has the designation "KHP_WRITE_NO_LOCK".
Functions, which cannot be executed when know-how protection is active
The following functions cannot be executed when know-how protection is active:
Download
Automatic controller setting
Stationary/rotating measurement
Clear fault buffer
Create acceptance documentation
Functions that can be executed optionally when know-how protection is active
The functions listed below can be executed for activated know-how protection provided
diagnostic functions were permitted when it was activated:
Trace function
Function generator
Measuring functions
Setting parameters, which can only be read when know-how protection is active
The following setting parameters cannot be changed, but can be read, when know-how
protection is activated:
Motor parameters (p0100, p0300, p0304, p0305, p0349)
Data sets (p0120, p0130, p0140, p0150, p0170, p0180)
Encoder type (p0400)
Reference quantities (p2000, p2001, p2002, p2003, p2005, p2006, p2007)
These parameters are shown in STARTER in the expert list with a gray background.