EasyManua.ls Logo

Siemens SINAMICS G130 - Page 107

Siemens SINAMICS G130
610 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Electrical installation
4.10 Signal connections
Inverter chassis units
Operating Instructions, 07/2016, A5E00331449A
107
X530: 4 digital inputs
Table 4- 37 Terminal block X530
Terminal
Designation
1)
Technical data
1
DI 4
Voltage
: - 3 … +30 V
Current consumption
typical: 10 mA at 24 V DC
Input delay
:
For "0" to "1": Typ. 50 µs max. 100 µs
for "1" to "0": Typ. 130 µs, max. 150 µs
Electrical isolation
:
Reference potential is terminal M2
Signal level
(including ripple)
High level: 15 … 30 V
Low-level: -3 … +5 V
2 DI 5
3
DI 6
4
DI 7
5
M2
6 M
Max. connectable cross-section: 1.5 mm²
1)
DI: digital input; M2: ground reference; M: Electronics ground
Note
Ensuring the function of digital inputs
An open input is interpreted as "low".
To enable the digital inputs (DI) to
function, terminal M2 must be connected.
This is achieved through one of the following measures:
1.
Also route the reference ground of the digital inputs.
2.
A jumper to terminal M. (
Note:
This removes the electrical isolation for these digital
inputs.)

Table of Contents

Other manuals for Siemens SINAMICS G130

Related product manuals