Electrical installation
4.10 Signal connections
Inverter chassis units
Operating Instructions, 07/2016, A5E00331449A
109
S5: Selector for voltage/current AI0, AI1
Table 4- 39 Selector for voltage/current S5
Switch
Function
S5.0
Selector voltage (V) / current (I) Al0
S5.1
Selector voltage (V) / current (I) Al1
Note
Delivery condition
When delivered, both switches are set to voltage measurement (switch set to "V").
X522: 2 analog outputs, temperature sensor connection
Table 4- 40 Terminal block X522
Terminal
Designation
1)
Technical data
1
AO 0V+
You can set the following output signals using pa-
rameters:
Voltage
: -10 … +10 V (max. 3 mA)
Current 1
: 4 … 20 mA (max. load resistance
500 Ω)
Current 2
: -20 … +20 mA (max. load resistance
500 Ω)
Current 3
: 0 … 20 mA (max. load resistance
500 Ω)
Resolution: 11 bits + sign
Continuously short-circuit proof
2
AO 0-
3
AO 0C+
4
AO 1V+
5
AO 1-
6 AO 1C+
7
+Temp
2)
Temperature sensor KTY84-1C130/PT1000/PTC
Measuring current via temperature sensor connec-
tion: 2 mA
8 -Temp
2)
Max. connectable cross-section: 1.5 mm²
1)
AO xV: analog output voltage; AO xC: Analog output current
2)
Accuracy of the temperature measurement:
- KTY: ±7 °C (including evaluation)
- PT1000: ±5 °C (PT1000 tolerance class B according to EN 60751 including evaluation)
- PTC: ±5 °C (including evaluation)
WARNING
Danger to life due to electric shock in the event of voltage flashovers at the temperature
sensor
Voltage flashovers in the signal electronics can occur in motors without safe electrical
separation of the temperature sensors.
Use temperature sensors that fully comply with the specifications of the safety isolation.