Electrical installation
4.10 Signal connections
Inverter chassis units
120 Operating Instructions, 07/2016, A5E00331449A
X521 / X531: Encoder connection 2 for HTL/TTL encoder with open-circuit monitoring
Table 4- 50 Encoder connection X521
2 A* Inverse incremental signal A
Inverse incremental signal B
Inverse reference signal R
Max. connectable cross-section: 1.5 mm²
Note
Operation of unipolar HTL encoders
When unipolar HTL encoders are used, A*, B*, and R* on the terminal block must be
jumpered with M_Encoder (X531).
Table 4- 51 Encoder connection X531
Ground for encoder power supply
3 -Temp
1)
Temperature sensor KTY84-1C130 /
4 +Temp
1)
Temperature sensor KTY84-1C130 /
5 Reserved, do not use
Max. connectable cross-section: 1.5 mm²
Measuring current via temperature sensor connection: 2 mA
Accuracy of the temperature measurement:
- KTY: ±7 °C (including evaluation)
- PT1000: ±5 °C (PT1000 tolerance class B according to EN 60751 including evaluation)
- PTC: ±5 °C (including evaluation)