Operation
6.5 Setpoint sources
Inverter chassis units
Operating Instructions, 07/2016, A5E00331449A
213
r4052
Actual input voltage/current
p4053
Analog inputs smoothing time constant
r4055
Current referenced input value
p4056
p4057
Analog inputs, characteristic value x1
p4058
Analog inputs, characteristic value y1
p4059
characteristic value x2
p4060
Analog inputs, characteristic value y2
p4063
Note
Delivery condition
In the factory setting and after basic commissioning, an input voltage of 10
V is equal to the
main setpoint 100% reference speed
(p2000), which has been set to the maximum speed
Example: Switching analog input 0 from voltage to current input 0 to 20 mA
Current/voltage switchover
Set current/voltage selector to "Current" ("I").
Set analog input type 0 to 0 ... 20 mA.
Note
Save changes so that they are protected against power failure
The change to the analog input must then be stored on the CompactFlash card so that it is
protected in the event of a power failure.