Operation
6.6 Communication according to PROFIdrive
Inverter chassis units
234 Operating Instructions, 07/2016, A5E00331449A
Table 6- 16 Parameter request
Request header
Request reference = 25 hex
Number of parameters = 01 hex
Parameter address
Number of elements = 08 hex
Parameter no. = 945 dec 6
Information about the parameter request:
● Request reference:
The value is selected at random from the valid value range. The request reference
establishes the relationship between request and response.
● Request identifier:
01 hex → This identifier is required for a read request.
● Axis:
02 hex → Drive 2, fault buffer with drive- and device-specific faults
● Number of parameters:
01 hex → One parameter is read.
● Attribute:
10 hex → The parameter values are read.
● Number of elements:
08 hex → The actual fault incident with eight faults is to be read.
● Parameter number:
945 dec → p0945 (fault code) is read.
● Subindex:
0 dec → Reading starts at index 0.
If STW1.3 = "1" → Initiate parameter request
Table 6- 17 Parameter response
Response header
Request reference mirrored = 25 hex
Axis mirrored = 02 hex Number of parameters =
2 + 3
Parameter value
Number of values = 08 hex