Operation 
  6.6 Communication according to PROFIdrive 
Inverter chassis units 
Operating Instructions, 07/2016, A5E00331449A 
243 
The other diagnostics data (types) can be in any sequence. This is the reason that the 
following diagnostics data include a header: 
●  Identifier-related diagnostics 
●  Status messages/module status 
●  Channel-related diagnostics 
The diagnostic data type can be uniquely identified based on the header. 
 
must operate in the DPV1 mode.  
For communication via PROFIBUS, standard diagnostics is structured as follows. 
 
1  Station 
status 1 
Master_ 
Lock 
= 0 
Prm_Fault  0  Not_ 
Supported 
  Cfg_Fault  Station_ 
Not_ 
Ready 
Station_ 
Non_ 
Exist 
2  Station 
0  0  Sync_ 
Freeze_ 
WD_On  1  Stat_Diag 
Prm_Req 
3  Station 
status 3 
 
 
0  0  0  0  0  0  0 
 
Ident_Number (HighByte) of the slave 
Ident_Number (LowByte) of the slave 
In this context, the following values are decisive for diagnostics: 
●  Ext_Diag 
–  Group signal for diagnostics in the slave 
–  = 1, if at least 1 alarm is active 
●  Ext_Diag_Overflow 
Display, diagnostics overflow in the slave (for more than 240 bytes)