EasyManua.ls Logo

Siemens SINAMICS G130 - Page 281

Siemens SINAMICS G130
610 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Operation
6.9 Communication via SINAMICS Link
Inverter chassis units
Operating Instructions, 07/2016, A5E00331449A
281
9. Define the receive data for node 2:
Specify that the data placed in the receive buffer p8872 of node 2 in locations 0 to 4 is
received from node 1:
p8872[0] = 1
p8872[1] = 1
p8872[2] = 1
p8872[3] = 1
p8872[4] = 1
Specify that PZD1, PZD2 and PZD3 of node 1 are to be placed in the receive buffer
p8870 of node 2 in locations 0 to 4:
p8870[0] = 1 (PZD1)
p8870[1] = 2 (PZD2 1st part)
p8870[2] = 3 (PZD2 2nd part)
p8870[3] = 4 (PZD3 1st part)
p8870[4] = 5 (PZD3 2nd part)
r2050[0], r2060[1] and r2060[3] subsequently contain (after step 13) the values of
PZD 1, PZD 2 and PZD 3 of node 1.
10.Define the send data for node 2:
Specify the PZD that node 2 should send:
:p2051[0] = drive1:r0899 (PZD length is 1 word)
Place this PZD in the send buffer (p8871) of node 2:
p8871[0] = 1
11.Define the receive data for node 1:
Specify the data that should be placed in the receive buffer p8872 of node 1 in
location 0, received from node 2:
p8872[0] = 2
Define that PZD1 of node 2 is saved in the receive buffer p8870 of node 1 in location
0:
p8870 [ 0] = 1
r2050[0] subsequently contains (after step 13) the value of PZD 1 of node 2.
12.At the two nodes carry-out a "Copy RAM to ROM" to backup the parameterization and the
data.
13.Set p8842 =1, to activate parameters p8870, p8871 and p8872.

Table of Contents

Other manuals for Siemens SINAMICS G130

Related product manuals