Setpoint channel and closed-loop control 
  7.4 Vector speed/torque control with/without encoder 
Inverter chassis units 
Operating Instructions, 07/2016, A5E00331449A 
355 
Example of speed-dependent adaptation 
 
Figure 7-18  Example of speed-dependent adaptation 
For operation without encoder, a higher value is in p1464 than in p1465. As a consequence, 
the behavior is inverted: Kp increases with increasing speed and Tn decreases. 
Special case, encoderless operation in the field-weakening range 
In encoderless operation, dynamic reduction for the field-weakening range can be activated 
with p1400.0 = 1. 
Kp/Tn ∼ flux setpoint  
Kp/Tn decreases proportionally with the flux setpoint (minimum: factor 0.25).  
This dynamic reduction is activated to reduce the controller dynamic response in the field-
weakening range. Up to the field-weakening range, the higher controller dynamic of the 
speed controller is kept. 
 
Speed controller adaptation (Kp_n/Tn_n adaptation) 
 
  p1400.5 
Speed control configuration: Kp/Tn adaptation active
 
  p1400.6 
Speed control configuration: Free Tn adaptatio
n active 
  p1470 
Speed controller encoderless operation P gain
 
  p1472 
Speed controller encoderless operation integral time