EasyManua.ls Logo

Siemens SINAMICS G130 - Page 355

Siemens SINAMICS G130
610 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Setpoint channel and closed-loop control
7.4 Vector speed/torque control with/without encoder
Inverter chassis units
Operating Instructions, 07/2016, A5E00331449A
355
Example of speed-dependent adaptation
Figure 7-18 Example of speed-dependent adaptation
For operation without encoder, a higher value is in p1464 than in p1465. As a consequence,
the behavior is inverted: Kp increases with increasing speed and Tn decreases.
Special case, encoderless operation in the field-weakening range
In encoderless operation, dynamic reduction for the field-weakening range can be activated
with p1400.0 = 1.
Kp/Tn flux setpoint
Kp/Tn decreases proportionally with the flux setpoint (minimum: factor 0.25).
This dynamic reduction is activated to reduce the controller dynamic response in the field-
weakening range. Up to the field-weakening range, the higher controller dynamic of the
speed controller is kept.
Function diagram
FP 6050
Speed controller adaptation (Kp_n/Tn_n adaptation)
Parameters
p1400.5
Speed control configuration: Kp/Tn adaptation active
p1400.6
Speed control configuration: Free Tn adaptatio
n active
p1470
Speed controller encoderless operation P gain
p1472
Speed controller encoderless operation integral time

Table of Contents

Other manuals for Siemens SINAMICS G130

Related product manuals