Functions, monitoring, and protective functions
9.2 Drive functions
Inverter chassis units
Operating Instructions, 07/2016, A5E00331449A
415
Restrictions
Pulse frequency wobbling can only be activated under the following conditions (p1810.2 =
1):
The drive is pulse suppressed.
p1800 < 2 x 1000 / p0115[0]
p1811 (Pulse frequency wobbling amplitude) can only be set under the following
conditions:
p1802.2 = 1
p0230 (output filter) < 3 (no sine-wave filter)
When pulse frequency wobbling is activated and impulses are enabled, the maximum
pulse frequency (p1800) can be set as follows:
For p1811 = 0: p1800 2 x 1000 / p0115[0]
For p1811 > 0: p1800 ≤ 1000 / p0115[0]
When pulse frequency wobbling is activated and impulses are enabled, if the maximum
pulse frequency (p1800) is set to be greater than 1000 / p0115[0], then p1811 is set to 0.
When pulse frequency wobbling is activated and impulses are suppressed, if the
maximum pulse frequency (p1800) is set to be greater than 2 x 1000 / p0115[0], then
p1811 and p1810.2 are set to 0.
Note
Disable pulse frequency wobbling
If pulse freque
ncy wobbling is deactivated (p1810.2 = 0), then all the indices of parameter
p1811 are set to 0.
Parameter
p1800
Pulse frequency setpoint
p1810.2
Wobbling activated
p1811[D]
Pulse frequency wobbling amplitude