Technical specifications
12.3 Technical specifications
Inverter chassis units
578 Operating Instructions, 07/2016, A5E00331449A
- Line protection
without semiconductor protection
Rated current
frame size to IEC 60269
- Line and semiconductor protection
Rated current
A
A
3NA3240-6
200
2
3NE1225-2
200
3NA3244-6
250
2
3NE1227-2
250
3NA3252-6
315
2
3NE1230-2
315
Minimum short-circuit current
5)
Rated output of a typ. 6-pole standard induction motor based on I
L
or I
H
at 690 V 3 AC 50 Hz.
The base-load current I
L
is based on a duty cycle of 110% for 60 s or 150% for 10 s with a duty cycle duration of 300 s
(see "Overload capability").
The base-load current I
H
is based on a duty cycle of 150% for 60 s or 160% for 10 s with a duty cycle duration of 300 s
(see "Overload capability").
If the auxiliary supply is to be fed in separately from the load supply, e.g., if the control should be able to continue com-
munication if the line voltage fails.
5)
The minimum current required to reliably trigger 3NE1 protective devices.