Electrical installation
4.10 Signal connections
Inverter chassis units
74 Operating Instructions, 07/2016, A5E00331449A
Fire hazard due to overheating when permissible connection cable lengths are exceeded
Excessively long connection cables connected to terminal strip X46 can cause components
to overheat with the associated risk of fire and smoke.
• Limit the length of the connecting cables to a maximum of 10 m.
• Do not route the connection cable outside the control cabinet or control cabinet group.
X400 – X402: DRIVE-CLiQ interface
Table 4- 13 DRIVE-CLiQ interface X400 – X402: Power Module
1 TXP Transmit data +
Blanking plate for DRIVE-CLiQ interfaces (50 pcs.) Article number: 6SL3066-4CA00-0AA0