Electrical installation
4.10 Signal connections
Inverter chassis units
86 Operating Instructions, 07/2016, A5E00331449A
Note
Address 126 is used for commissioning.
Permitted PROFIBUS addresses are 1 ... 126.
When several Control Units are connected to a PROFIBUS line, you set the addresses
differently than for the factory setting. Each PROFIBUS address in a PROFIBUS line can
only be assigned once. Either set the PR
OFIBUS address in absolute terms using the rotary
coding switches
or selectively in parameter p0918. Each change made to the bus address
is not effective until POWER ON.
The currently set address of the rotary coding switch is displayed in parameter r205
7.
X127: LAN (Ethernet)
Table 4- 20 X127 LAN (Ethernet)
Pin
Designation
Technical data
1
TXP
Ethernet transmit data +
2
TXN
Ethernet transmit data -
3 RXP Ethernet receive data +
4
Reserved, do not use
5
Reserved, do not use
6
RXN
Ethernet receive data -
7
Reserved, do not use
8
Reserved, do not use
Connector type: RJ45 socket
Note
The LAN (Ethernet) interface does not support Auto MDI(X). For this reason, only crossover
cables may be used to
connect devices.
For diagnostic purposes, the X127 LAN interface features a green and a yellow LED. These
LEDs indicate the following status information:
Table 4- 21 LED statuses for the X127 LAN interface
LED
Color
State
Description
Link port
-
Off
Missing or faulty link
Green
Continuous light
10 or 100 Mbit link available
Activity port
-
Off
No activity
Yellow
Flashing light
Sending or receiving