Electrical installation   
4.10 Signal connections 
  Inverter chassis units 
96  Operating Instructions, 07/2016, A5E00331449A 
X132: Digital inputs/outputs 
Table 4- 26  Terminal block X132 
 
Voltage (max.): -3 … +30 VDC 
Current consumption, typical: 9 mA at 24 V 
Electrical isolation: The reference potential is terminal M2 
Level (including ripple) 
High level: 15 … 30 V 
Low-level: -3 … +5 V 
Input delay (typ.): 
For "0" → "1": 50 μs 
2  DI 5 
6  DI 21 
Reference potential for terminal 1 ... 6 
:  
Voltage: -3 … +30 VDC 
Current consumption, typical: 9 mA at 24 V 
Level (including ripple) 
High level: 15 … 30 V 
Low-level: -3 … +5 V 
DI/DO 12, 13, 14, and 15 are "high-speed inputs" 
2)
 
Input delay (typ.): 
For "0" → "1": 5 μs 
For "1" → "0": 50 μs 
: 
Voltage: 24 V DC 
Max. load current per output: 500 mA 
Continuous short-circuit proof 
Output delay (typ./max.): 
3)
 
For "0" → "1": 150 μs / 400 μs 
For "1" → "0": 75 μs / 100 μs 
Switching frequency: 
For resistive load: Max. 100 Hz 
For inductive load: Max. 0.5 Hz 
For lamp load: Max. 10 Hz 
14  M 
Max. connectable cross-section: 1.5 mm² 
  DI: digital input; DI/DO: bidirectional digital input/output; M: Electronics ground; M2: reference potential 
  The rapid inputs can be used as probe inputs or as inputs for the external zero mark 
3) 
  Data for: V
cc
 = 24 V; load 48 Ω; high ("1") = 90% V
out
; low ("0") = 10% V
out
 
The maximum cable length that can be connected is 30 m.