EasyManuals Logo

Siemens SIPROTEC 4 User Manual

Siemens SIPROTEC 4
734 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #186 background imageLoading...
Page #186 background image
The displacement voltage element of the sensitive ground fault detection, the directional overcurrent protec-
tion (phase and ground function), the voltage-controlled inverse time non-directional overcurrent protection,
the undervoltage protection and the synchronization function are blocked if parameter 5310 BLOCK PROT. is
set to YES.
The FFM picks up if the ground voltage V
N
is higher than the set limit value under address5302 FUSE FAIL
3Vo and if the ground current IN lies below the set limit value under address 5303 FUSE FAIL RESID.
Pickup occurs in accordance with the configured values. A hysteresis of 105% for the dropout is integrated for
Ι
N
or 95% for V
N
. In case of low-current asymmetrical faults in systems with week infeed, the ground current
caused by the fault could lie below the pickup threshold of the Fuse Failure Monitor. Overfunctioning of the
Fuse Failure Monitor can, however, cause the feeder protection device to underfunction since all protection
functions that use voltage signals are blocked. In order to prevent overfunctioning of the FFM, the phase
currents are also checked. If at least one phase current lies above the pickup threshold of 5303 FUSE FAIL
RESID, it can be assumed that the zero current created by a fault will equally exceed this threshold.
In order to immediately detect an existing fault after switching in, the following applies: If a ground current Ι
N
is detected within 10 seconds after recognition of the Fuse Failure criterion, the protection assumes a fault
and removes the blocking by the Fuse Failure Monitor for the duration of the fault. If, on the other hand, the
voltage failure criterion is present for longer than approx. 10 s, the blocking is permanently activated. After
this time has elapsed, it can be assumed that a fuse failure has actually occurred. Only 10 s after the voltage
criterion has been removed by correction of the secondary circuit failure, will the blocking automatically reset,
thereby releasing the blocked protection functions.
The generation of the internal signal “Alarm FFM” for the operation in isolated systems is shown in
Figure 2-74.
Functions
2.12 Monitoring Functions
186 SIPROTEC 4, 7SJ62/64, Manual
C53000-G1140-C207-8, Edition 08.2016

Table of Contents

Other manuals for Siemens SIPROTEC 4

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 4 and is the answer not in the manual?

Siemens SIPROTEC 4 Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 4
CategoryProtection Device
LanguageEnglish

Related product manuals