EasyManua.ls Logo

Siemens SIPROTEC 4 - Interaction with Fuse Failure Monitor (FFM)

Siemens SIPROTEC 4
734 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
The dropout curve may be user-defined as well. This is advantageous when the overcurrent protection must
be coordinated with conventional electromechanical overcurrent relays located towards the source. If no user-
defined dropout curve is required, the element drops out as soon as the measured signal is less than approx.
95% of the pickup setting. When a new pickup is evoked, the timer starts at zero again.
The following figure shows by way of an example the logic diagram for the 67-TOC relay element of the direc-
tional inverse time overcurrent protection of the phase currents.
[7sj6x_gerueberstromzeit_abh_ueberstrom_ip-150502-kn, 1, en_US]
Figure 2-27
Logic diagram for the directional overcurrent protection: 67-TOC relay element
Interaction with Fuse Failure Monitor (FFM)
False or undesired tripping can be caused by a measuring voltage that can be caused by either short-circuit or
broken wire in the voltage transformer's secondary system or an operation of the voltage transformer fuse.
2.3.5
Functions
2.3 Directional Overcurrent Protection 67, 67N
92 SIPROTEC 4, 7SJ62/64, Manual
C53000-G1140-C207-8, Edition 08.2016

Table of Contents

Other manuals for Siemens SIPROTEC 4

Related product manuals