Interaction with Automatic Reclosing Function (ground)
If reclosing follows, high-speed and simultaneous closing in the event of a fault with 67N-2 is usually desired.
If the fault still exists after reclosing, the 67N-1 or 67N-TOC element is initiated with graded tripping times,
that is, the 67N-2 or 67N-3 element is blocked. For this purpose, parameter 1614 67N-2 active or 1632
67N-3 active is used to determine whether the 67N-2 or 67N-3 element is influenced by the release signal
of the internal or an external automatic reclosing device or not. The setting with 79 active means that the
67N- 2 or 67N-3 element is only released if the automatic reclosing function is not blocked. If this is not
desired, the setting always is selected so that the 67N-2 or 67N-3 element is always active as configured.
The integrated automatic reclosing function of 7SJ62/64 also provides the option to individually determine for
each overcurrent element whether tripping or blocking is to be carried out instantaneously, unaffected by the
AR with time delay (see Section 2.16 Automatic Reclosing System 79).
Settings
Addresses which have an appended “A” can only be changed with DIGSI, under “Additional Settings”.
The table indicates region-specific presettings. Column C (configuration) indicates the corresponding secon-
dary nominal current of the current transformer.
Addr. Parameter C Setting Options Default Setting Comments
1501 FCT 67/67-TOC OFF
ON
OFF 67, 67-TOC Phase Time
Overcurrent
1502 67-2 PICKUP 1A 0.10 .. 35.00 A; ∞ 2.00 A 67-2 Pickup
5A 0.50 .. 175.00 A; ∞ 10.00 A
1503 67-2 DELAY 0.00 .. 60.00 sec; ∞ 0.10 sec 67-2 Time Delay
1504 67-1 PICKUP 1A 0.10 .. 35.00 A; ∞ 1.00 A 67-1 Pickup
5A 0.50 .. 175.00 A; ∞ 5.00 A
1505 67-1 DELAY 0.00 .. 60.00 sec; ∞ 0.50 sec 67-1Time Delay
1507 67-TOC PICKUP 1A 0.10 .. 4.00 A 1.00 A 67-TOC Pickup
5A 0.50 .. 20.00 A 5.00 A
1508 67 TIME DIAL 0.05 .. 3.20 sec; ∞ 0.50 sec 67-TOC Time Dial
1509 67 TIME DIAL 0.50 .. 15.00 ; ∞ 5.00 67-TOC Time Dial
1510 67-TOC Drop-out Instantaneous
Disk Emulation
Disk Emulation Drop-Out Characteristic
1511 67- IEC CURVE Normal Inverse
Very Inverse
Extremely Inv.
Long Inverse
Normal Inverse IEC Curve
1512 67- ANSI CURVE Very Inverse
Inverse
Short Inverse
Long Inverse
Moderately Inv.
Extremely Inv.
Definite Inv.
Very Inverse ANSI Curve
1513A MANUAL CLOSE 67-3 instant.
67-2 instant.
67-1 instant.
67-TOC instant.
Inactive
67-2 instant. Manual Close Mode
1514A 67-2 active with 79 active
always
always 67-2 active
2.3.11
Functions
2.3 Directional Overcurrent Protection 67, 67N
106 SIPROTEC 4, 7SJ62/64, Manual
C53000-G1140-C207-8, Edition 08.2016