7SJ640 Approx. 5 W Approx. 9 W
7SJ641 Approx. 5,5 W Approx. 13 W
7SJ642 Approx. 5,5 W Approx. 12 W
7SJ645 Approx. 6,5 W Approx. 15 W
7SJ647 Approx. 7,5 W Approx. 21 W
Bridging time for failure/short-circuit, IEC 60255-
11 (in not energized operation)
≥ 50 ms at V ≥ DC 110 V
≥ 20 ms at V ≥ DC 24 V
Alternating Voltage
Voltage Supply via Integrated Converter
Rated auxiliary voltage AC V
Aux
AC 115 V AC 230 V
Permissible Voltage Ranges AC 92 V to 132 V AC 184 V to 265 V
Power input (at AC 115 V/ 230 V) Quiescent Energized
7SJ62 Approx. 3 VA Approx. 9 VA
7SJ640 Approx. 7 VA Approx. 12 VA
7SJ641 Approx. 9 VA Approx. 19,5 VA
7SJ642 Approx. 9 VA Approx. 18,5 VA
7SJ645 Approx. 12 VA Approx. 23 VA
7SJ647 Approx. 16 VA Approx. 33 VA
Bridging Time for Failure/Short-Circuit
(in not energized operation)
200 ms
Binary Inputs and Outputs
Binary Inputs
Variant
Number
7SJ621*- 8 (configurable)
7SJ622*- 11 (configurable)
7SJ623*- 8 (configurable)
7SJ624*- 11 (configurable)
7SJ625*- 8 (configurable)
7SJ626*- 11 (configurable)
7SJ640*- 7 (configurable)
7SJ641*- 15 (configurable)
7SJ642*- 20 (configurable)
7SJ645*- 33 (configurable)
7SJ647*- 48 (configurable)
Rated voltage range DC 24 V to 250 V, bipolar
7SJ62 – – – BI1 ... BI11
7SJ640 – – – BI1 ... 7
7SJ641 – – – BI1 ... 15
7SJ642 BI8... 19 BI1 ... 7; BI20
7SJ645 BI8... 19; BI21...32 BI1...7; BI20; BI33
7SJ647 BI8... 19; BI21...32 BI1...7; BI20; BI33...48
Current consumption, picked up
(independent of the operating voltage)
approx. 0,9 mA approx. 1.8 mA
4.1.3
Technical Data
4.1 General Device Data
SIPROTEC 4, 7SJ62/64, Manual 439