V
0
, the thermal measured value of overload protection Θ/Θ
off
, the real power P, reactive power Q, and appa-
rent power S, the frequency; and the power factor cos ϕ are calculated as primary values (including the date
and time they were last updated).
The minimum and maximum values of the long-term averages listed in the previous section are also calcu-
lated.
The minimum and maximum values can be reset at any time via binary inputs or by using the integrated
control panel or the DIGSI software. Additionally, the reset can be carried out cyclically, starting at a preset
point of time.
Setting Notes
Minimum and Maximum Values
The tracking of minimum and maximum values can be reset automatically at a programmable point in time.
To select this feature, address 8311 MinMax cycRESET should be set to YES. The point in time when reset is
to take place (the minute of the day in which reset will take place) is set at address 8312 MiMa RESET TIME.
The reset cycle in days is entered at address 8313 MiMa RESETCYCLE, and the beginning date of the cyclical
process, from the time of the setting procedure (in days), is entered at address 8314 MinMaxRES.START.
Settings
Addr. Parameter Setting Options Default Setting Comments
8311 MinMax cycRESET NO
YES
YES Automatic Cyclic Reset Function
8312 MiMa RESET TIME 0 .. 1439 min 0 min MinMax Reset Timer
8313 MiMa RESETCYCLE 1 .. 365 Days 7 Days MinMax Reset Cycle Period
8314 MinMaxRES.START 1 .. 365 Days 1 Days MinMax Start Reset Cycle in
Information List
No.
Information Type of
Informa-
tion
Comments
- ResMinMax IntSP_Ev Reset Minimum and Maximum counter
395 >I MinMax Reset SP >I MIN/MAX Buffer Reset
396 >I1 MiMaReset SP >I1 MIN/MAX Buffer Reset
397 >V MiMaReset SP >V MIN/MAX Buffer Reset
398 >VphphMiMaRes SP >Vphph MIN/MAX Buffer Reset
399 >V1 MiMa Reset SP >V1 MIN/MAX Buffer Reset
400 >P MiMa Reset SP >P MIN/MAX Buffer Reset
401 >S MiMa Reset SP >S MIN/MAX Buffer Reset
402 >Q MiMa Reset SP >Q MIN/MAX Buffer Reset
403 >Idmd MiMaReset SP >Idmd MIN/MAX Buffer Reset
404 >Pdmd MiMaReset SP >Pdmd MIN/MAX Buffer Reset
405 >Qdmd MiMaReset SP >Qdmd MIN/MAX Buffer Reset
406 >Sdmd MiMaReset SP >Sdmd MIN/MAX Buffer Reset
407 >Frq MiMa Reset SP >Frq. MIN/MAX Buffer Reset
408 >PF MiMaReset SP >Power Factor MIN/MAX Buffer Reset
412 > Θ MiMa Reset SP >Theta MIN/MAX Buffer Reset
837 IAdmdMin MVT I A Demand Minimum
838 IAdmdMax MVT I A Demand Maximum
839 IBdmdMin MVT I B Demand Minimum
840 IBdmdMax MVT I B Demand Maximum
2.25.5.2
2.25.5.3
2.25.5.4
Functions
2.25 Auxiliary Functions
SIPROTEC 4, 7SJ62/64, Manual 335
C53000-G1140-C207-8, Edition 08.2016