Table 2-3 Pickup Indications of Overcurrent Protection
Internal indication Figure Output indication FNo.
50-3 A PU
50-2 A PU
50-1 A PU
51 A PU
Figure 2-5
Figure 2-7
Figure 2-11
50/51 Ph A PU
1762
50-3 B PU
50-2 B PU
50-1 B PU
51 B PU
Figure 2-5
Figure 2-7
Figure 2-11
50/51 Ph B PU
1763
50-3 C PU
50-2 C PU
50-1 C PU
51 C PU
Figure 2-5
Figure 2-7
Figure 2-11
50/51 Ph C PU
1764
50N-3 PU
50N-2 PU
50N-1 PU
51N PU
Figure 2-6
Figure 2-9
Figure 2-12
50N/51NPickedup
1765
50-3 A PU
50-3 B PU
50-3 C PU
50-3 picked up
1767
50N-3 PU
50N-3 picked up
1768
50-2 A PU
50-2 B PU
50-2 C PU
Figure 2-5
Figure 2-5
Figure 2-5
50-2 picked up
1800
50N-2 PU Figure 2-6
50N-2 picked up
1831
50-1 A PU
50-1 B PU
50-1 C PU
Figure 2-7
Figure 2-7
Figure 2-7
50-1 picked up
1810
50N-1 PU Figure 2-6
50N-1 picked up
1834
51 A PU
51 B PU
51 C PU
Figure 2-11
Figure 2-11
Figure 2-11
51 picked up
1820
51N PU Figure 2-12
51N picked up
1837
(All pickups)
50(N)/51(N) PU
1761
In the trip signals, the element which initiated the tripping is also indicated.
Two-phase Overcurrent Protection (Only Non-Directional)
The 2-phase overcurrent protection functionality is used in isolated or grounded systems where interaction
with existing 2-phase protection equipment is required. As an isolated or grounded system remains opera-
tional with a 1-phase ground fault, this protection serves to detect double ground faults with high ground
fault currents. The respective feeder must be switched off only in this case. A 2-phase measurement is suffi-
cient for this purpose. In order to ensure selectivity of the protection in this section of the system, only phases
A and C are monitored.
If 250 50/51 2-ph prot (settable in P.System Data 1) is set to ON, Ι
B
is not used for threshold compar-
ison. If the fault is a simple ground fault in B, the element will not pick up. A double ground fault is assumed
only after pickup on A or C, causing the element to pick up and trip after the delay time has elapsed.
2.2.9
Functions
2.2 Overcurrent Protection 50, 51, 50N, 51N
SIPROTEC 4, 7SJ62/64, Manual 71
C53000-G1140-C207-8, Edition 08.2016

Table of Contents

Other manuals for Siemens SIPROTEC 4

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 4 and is the answer not in the manual?

Siemens SIPROTEC 4 Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 4
CategoryProtection Device
LanguageEnglish

Related product manuals