Addr. Parameter C Setting Options Default Setting Comments
6001 S1: RE/RL -0.33 .. 7.00 1.00 S1: Zero seq. compen-
sating factor RE/RL
6002 S1: XE/XL -0.33 .. 7.00 1.00 S1: Zero seq. compen-
sating factor XE/XL
6003 S1: x' 1A 0.0050 .. 15.0000 Ω/mi 0.2420 Ω/mi S1: feeder reactance per
mile: x'
5A 0.0010 .. 3.0000 Ω/mi 0.0484 Ω/mi
6004 S1: x' 1A 0.0050 .. 9.5000 Ω/km 0.1500 Ω/km S1: feeder reactance per
km: x'
5A 0.0010 .. 1.9000 Ω/km 0.0300 Ω/km
6005 S1: Line angle 10 .. 89 ° 85 ° S1: Line angle
6006 S1: line length 0.1 .. 650.0 Miles 62.1 Miles S1: Line length in miles
6007 S1: Line length 0.1 .. 1000.0 km 100.0 km S1: Line length in kilometer
6011 S2: RE/RL -0.33 .. 7.00 1.00 S2: Zero seq. compen-
sating factor RE/RL
6012 S2: XE/XL -0.33 .. 7.00 1.00 S2: Zero seq. compen-
sating factor XE/XL
6013 S2: x' 1A 0.0050 .. 15.0000 Ω/mi 0.2420 Ω/mi S2: feeder reactance per
mile: x'
5A 0.0010 .. 3.0000 Ω/mi 0.0484 Ω/mi
6014 S2: x' 1A 0.0050 .. 9.5000 Ω/km 0.1500 Ω/km S2: feeder reactance per
km: x'
5A 0.0010 .. 1.9000 Ω/km 0.0300 Ω/km
6015 S2: Line angle 10 .. 89 ° 85 ° S2: Line angle
6016 S2: line length 0.1 .. 650.0 Miles 62.1 Miles S2: line length in miles
6017 S2: Line length 0.1 .. 1000.0 km 100.0 km S2: Line length in kilometer
6021 S3: RE/RL -0.33 .. 7.00 1.00 S3: Zero seq. compen-
sating factor RE/RL
6022 S3: XE/XL -0.33 .. 7.00 1.00 S3: Zero seq. compen-
sating factor XE/XL
6023 S3: x' 1A 0.0050 .. 15.0000 Ω/mi 0.2420 Ω/mi S3: feeder reactance per
mile: x'
5A 0.0010 .. 3.0000 Ω/mi 0.0484 Ω/mi
6024 S3: x' 1A 0.0050 .. 9.5000 Ω/km 0.1500 Ω/km S3: feeder reactance per
km: x'
5A 0.0010 .. 1.9000 Ω/km 0.0300 Ω/km
6025 S3: Line angle 10 .. 89 ° 85 ° S3: Line angle
6026 S3: line length 0.1 .. 650.0 Miles 62.1 Miles S3: line length in miles
6027 S3: Line length 0.1 .. 1000.0 km 100.0 km S3: Line length in kilometer
Information List
No.
Information Type of
Informa-
tion
Comments
126 ProtON/OFF IntSP Protection ON/OFF (via system port)
356 >Manual Close SP >Manual close signal
501 Relay PICKUP OUT Relay PICKUP
511 Relay TRIP OUT Relay GENERAL TRIP command
533 Ia = VI Primary fault current Ia
534 Ib = VI Primary fault current Ib
535 Ic = VI Primary fault current Ic
561 Man.Clos.Detect OUT Manual close signal detected
2720 >Enable ANSI#-2 SP >Enable 50/67-(N)-2 (override 79 blk)
4601 >52-a SP >52-a contact (OPEN, if bkr is open)
2.1.6.4
Functions
2.1 General
SIPROTEC 4, 7SJ62/64, Manual 55
C53000-G1140-C207-8, Edition 08.2016