Commissioning Aids
Device data sent to a central or master computer system during test mode or commissioning can be influ-
enced. There are tools for testing the system interface and the binary inputs and outputs of the device.
Applications
Test Mode
Commissioning
Prerequisites
In order to be able to use the commissioning aids described in the following:
The device needs a port..
The device must be connected to a control center.
Description
Test Messages to the SCADA Interface during Test Operation
If the device is connected to a central or main computer system via the SCADA interface, then the information
that is transmitted can be influenced.
Depending on the type of protocol, all messages and measured values transferred to the central control
system can be identified with an added message "test operation"-bit while the device is being tested on site
(test mode). This identification prevents the messages from being incorrectly interpreted as resulting from an
actual power system disturbance or event. As another option, all messages and measured values normally
transferred via the system interface can be blocked during the testing ("block data transmission").
Data transmission block can be accomplished by controlling binary inputs, by using the operating panel on the
device, or with a PC and DIGSI via the operator interface.
The SIPROTEC 4 System Manual describes in detail how to activate and deactivate test mode and blocked data
transmission.
Checking the System Interface
If the device features a system interface and uses it to communicate with the control center, the DIGSI device
operation can be used to test if messages are transmitted correctly.
A dialog box shows the display texts of all messages which were allocated to the system interface in the
configuration matrix. In another column of the dialog box you can specify a value for the messages you intend
to test (e.g. ON/OFF). After having entered password no. 6 (for hardware test menus) a message can be
generated. The corresponding message is issued and can be read out either from the event log of the
SIPROTEC 4 device or from the substation control system.
The procedure is described in detail in Chapter "Mounting and Commissioning".
Checking the Binary Inputs and Outputs
The binary inputs, outputs, and LEDs of a SIPROTEC 4 device can be individually and precisely controlled in
DIGSI. This feature can be used, for example, to verify control wiring from the device to substation equipment
(operational checks), during start-up.
A dialog box shows all binary inputs and outputs as well as LEDs of the device with their present status. The
operating equipment, commands, or messages that are configured (masked) to the hardware components are
also displayed. After having entered password no. 6 (for hardware test menus), it is possible to switch to the
opposite status in another column of the dialog box. Thus, you can energize every single output relay to check
the wiring between protected device and the system without having to create the alarm allocated to it.
The procedure is described in detail in Chapter "Mounting and Commissioning".
2.25.9
2.25.9.1
Functions
2.25 Auxiliary Functions
340 SIPROTEC 4, 7SJ62/64, Manual
C53000-G1140-C207-8, Edition 08.2016

Table of Contents

Other manuals for Siemens SIPROTEC 4

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 4 and is the answer not in the manual?

Siemens SIPROTEC 4 Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 4
CategoryProtection Device
LanguageEnglish

Related product manuals