Power Protection Application with Flexible Protection Function). If the checkmark of a function is removed, all
settings and configurations made previously will be lost. After re-selecting the function, all settings and
configurations are in default setting. Setting of the flexible function is done in DIGSI under “Parameters”,
“Additional Functions” and “Settings”“. The configuration is done as usual under “Parameters” and “Configura-
tion”.
Settings
Addr. Parameter Setting Options Default Setting Comments
103 Grp Chge OPTION Disabled
Enabled
Disabled Setting Group Change Option
104 OSC. FAULT REC. Disabled
Enabled
Enabled Oscillographic Fault Records
112 Charac. Phase Disabled
Definite Time
TOC IEC
TOC ANSI
User Defined PU
User def. Reset
Definite Time 50/51
113 Charac. Ground Disabled
Definite Time
TOC IEC
TOC ANSI
User Defined PU
User def. Reset
Definite Time 50N/51N
115 67/67-TOC Disabled
Definite Time
TOC IEC
TOC ANSI
User Defined PU
User def. Reset
Definite Time 67, 67-TOC
116 67N/67N-TOC Disabled
Definite Time
TOC IEC
TOC ANSI
User Defined PU
User def. Reset
Definite Time 67N, 67N-TOC
117 Coldload Pickup Disabled
Enabled
Disabled Cold Load Pickup
122 InrushRestraint Disabled
Enabled
Disabled 2nd Harmonic Inrush Restraint
127 50 1Ph Disabled
Enabled
Disabled 50 1Ph
130 S.Gnd.F.Dir.Ch cos φ / sin φ
V0/I0 φ mea.
cos φ / sin φ (sens.) Ground fault dir. character-
istic
2.1.1.3
Functions
2.1 General
34 SIPROTEC 4, 7SJ62/64, Manual
C53000-G1140-C207-8, Edition 08.2016