Siemens SIPROTEC 4 - 4.24 Synchronization Function

Siemens SIPROTEC 4
734 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Synchronization Function
Operating Modes
- Synchrocheck
- Asynchronous / Synchronous (only 7SJ64)
Additional Release Conditions
- Live bus / dead line,
- Dead bus / live line,
- Dead bus and dead line
- Bypassing
Voltages
Maximum operating voltage V
max
20 V to 140 V (phase-to-phase) Increments 1 V
Minimum operating voltage V
min
20 V to 125 V (phase-to-phase) Increments 1 V
V< for dead line
V> for live line
1 V to 60 V (phase-to-phase)
20 V to 140 V (phase-to-phase)
Increments 1 V
Increments 1 V
Primary transformer rated voltage V2N 0.10 kV to 800.00 kV Increments 0.01 kV
Tolerances 2 % of pickup value or 2 V
Dropout Ratios approx. 0.9 (V>) or 1.1 (V<)
Permissible Difference
Voltages differences V2>V1; V2<V1
Tolerance
0.5 V to 50.0 V (phase-tophase)
1 V
Increments 0.1 V
Frequency Difference f2>f1; f2<f1
Tolerance for 7SJ64
Tolerance for 7SJ62
0.01 Hz to 2.00 Hz
15 mHz
20 mHz
Increments 0.01 Hz
Angle Difference α2 > α1; α2 < α1 2° to 80° Increments 1°
Tolerance
Max. angle error 5° for Δf ≤ 1 Hz
10° for Δf >1 Hz
Circuit breaker
Circuit breaker operating time
0.01 s to 0.60 s Increments 0,01 s
Threshold ASYN / SYN
Frequency Difference F
Synchronous
0.01 Hz to 0.04 Hz Increments 0.01 Hz
Matching
Vector group matching via angle
0° to 360° Increments 1°
Different voltage transformer V1/V2 0.50 to 2.00 Increments 0.01
Times
Minimum Measuring Time
approx. 80 ms
Maximum duration T
SYN DURATION
0.01 s to 1200.00 s
or ∞ (disabled)
Increments 0.01 s
4.24
Technical Data
4.24 Synchronization Function
SIPROTEC 4, 7SJ62/64, Manual 501
C53000-G1140-C207-8, Edition 08.2016