Settings
Addresses which have an appended “A” can only be changed with DIGSI, under “Additional Settings”.
The table indicates region-specific presettings. Column C (configuration) indicates the corresponding secon-
dary nominal current of the current transformer.
Addr. Parameter Function C Setting Options Default Setting Comments
0 FLEXIBLE FUNC. Flx OFF
ON
Alarm Only
OFF Flexible Function
0 OPERRAT. MODE Flx 3-phase
1-phase
no reference
3-phase Mode of Operation
0 BLK f out of r Flx YES
NO
YES Block while Freq. is out of
range
0 MEAS. QUANTITY Flx Please select
Current
Voltage
P forward
P reverse
Q forward
Q reverse
Power factor
dV/dt rising
dV/dt falling
Frequency
df/dt rising
df/dt falling
Binary Input
Please select Selection of Measured
Quantity
0 MEAS. METHOD Flx Fundamental
True RMS
Positive seq.
Negative seq.
Zero sequence
Ratio I2/I1
Fundamental Selection of Measure-
ment Method
0 PICKUP WITH Flx Exceeding
Dropping below
Exceeding Pickup with
0 CURRENT Flx Ia
Ib
Ic
In
In sensitive
In2
Ia Current
F.2
Functions, Settings, Information
F.2 Settings
SIPROTEC 4, 7SJ62/64, Manual 617
C53000-G1140-C207-8, Edition 08.2016