Open matrix in DIGSI
Rename the neutral message texts in accordance with the application.
Check configurations on contacts and in operation and fault buffer, or set them according to the require-
ments.
Further Information
The following instruction should be noted:
As the power factor does not differentiate between capacitive and inductive, the sign of the reactive
power may be used with CFC-help as an additional criterion.
Settings
Addresses which have an appended “A” can only be changed with DIGSI, under “Additional Settings”.
The table indicates region-specific presettings. Column C (configuration) indicates the corresponding secon-
dary nominal current of the current transformer.
Addr. Parameter C Setting Options Default Setting Comments
0 FLEXIBLE FUNC. OFF
ON
Alarm Only
OFF Flexible Function
0 OPERRAT. MODE 3-phase
1-phase
no reference
3-phase Mode of Operation
0 BLK f out of r YES
NO
YES Block while Freq. is out of
range
0 MEAS. QUANTITY Please select
Current
Voltage
P forward
P reverse
Q forward
Q reverse
Power factor
dV/dt rising
dV/dt falling
Frequency
df/dt rising
df/dt falling
Binary Input
Please select Selection of Measured
Quantity
0 MEAS. METHOD Fundamental
True RMS
Positive seq.
Negative seq.
Zero sequence
Ratio I2/I1
Fundamental Selection of Measurement
Method
0 PICKUP WITH Exceeding
Dropping below
Exceeding Pickup with
2.19.3
Functions
2.19 Flexible Protection Functions
278 SIPROTEC 4, 7SJ62/64, Manual
C53000-G1140-C207-8, Edition 08.2016